Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00225
Parcel: 141018940

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00225
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2010 DAVE MANN FIRE REVIEW Approved
02/03/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C-1; APPLICABLE CODES: THE CITY OF TUCSON REQUIRES USE OF THE ICC/ANSI A117.1-2003 EDITION. REVISE.
2. SHEET C-1; INDEX OF DRAWINGS: CHANGE DP DESIGNATION FOR EXISTING DEVELOPMENT PLAN TO C.2.
3. SHEET C-1; CODE REVIEW: PER THE CITY OF TUCSON COMMERCIAL SUBMITTAL REQUIREMENTS, A CODE REVIEW CHECKLIST SHALL BE COMPLETED AND SIGNED BY THE REGISTERED DESIGN PROFESSIONAL OF RECORD (FORM IS AVAILABLE ONLINE). INCLUDE THIS DATA ON SHEET C-1 OF THE DESIGN DRAWINGS.
4. SHEET A-2; FLOOR PLAN: THE SECTION DESIGNATIONS (A/A-3 AND B/A-3) NEED TO BE SHOWN ON THE PLAN.
5. SHEET A-2; PARTITION DETAIL: INDICATE THE GAGE OF THE METAL WALL STUDS.
6. SHEET A-2; PARTITION DETAIL: EXTEND THE DETAIL UP TO INCLUDE THE EXISTING STRUCTURE, NEW BLOCKING, CONNECTION OF THE BLOCKING TO THE EXISTING STRUCTURE, AND THE BLOCKING SIZE AND SPACING.
7. SHEET A-2; FLOOR PLAN: THESE REVISIONS ARE BEING MADE TO THE SECOND FLOOR LEVEL. PROVIDE A BUILDING ONE DIMENSIONED LAYOUT PLAN OF THE SECOND FLOOR (SIMILAR TO SHEET A1.1).
8. SHEET A-2; FLOOR PLAN: THE CORRIDOR CREATED IN THIS PROJECT MUST MEET THE FIRE RESISTANCE RATING REQUIREMENTS OF THE 2006 IBC, TABLE 1017.1. VERIFY THIS ON THE PLANS.
9. SHEET A-2; FLOOR PLAN: PROVIDE A COMPLETE MEANS OF EGRESS INDICATION ON THE PLAN.
10. SHEET A-3; FRAMING PLAN (KEYNOTE 2): SHOW A DETAIL ON THE DRAWINGS INDICATING HOW THE 6" METAL STUDS CONNECT TO THE 3 5/8" METAL TRACK.
11. SHEET A-3; FRAMING PLAN (KEYNOTE 3): PROVIDE THE METAL STUD GAGE AND A DETAIL OF THE BOX BEAM CONNECTION TO THE (2) 6" METAL STUDS.
12. SHEET A-3; FRAMING PLAN (KEYNOTE 4): PROVIDE THE GAGE OF THE METAL STUDS AT THE BOX BEAM.
13. SHEET A-3; FRAMING PLAN (KEYNOTE 4): PROVIDE A DETAIL OF THE BOX BEAM CONNECTION TO THE METAL STUD TRACK AT THE EXISTING CMU WALL.
14. SHEET A-3; FRAMING PLAN (KEYNOTE 4): PROVIDE A DETAIL OF THE CONNECTION OF THE 6" METAL JOISTS TO THE BOTTOM OF THE BOX BEAM.
15. SHEET A-3; FRAMING PLAN (KEYNOTE 5): EXPLAIN HOW THE HANGER WIRES CAN BE LOCATED "EACH WAY". THIS ADDS VERTICAL AND LATERAL LOADS TO THE BOTTOM CHORD OF THE EXISTING TRUSSES. ADDRESS THIS ISSUE.
16. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/03/2010 GERRY KOZIOL WWM REVIEW Passed
02/04/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/04/2010 ROBERT SHERRY WATER REVIEW Approved
02/04/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
02/04/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006.
02/05/2010 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
02/22/2010 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
02/24/2010 SUE REEVES REJECT SHELF Completed