Permit Number: T10CM00217
Parcel: 128114080

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00217
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Provide site drawing showing the size, route, and slope of the building sewer. Reference: Section 103.2.3, UPC 2006.
02/17/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/17/2010 ROBERT SHERRY WATER REVIEW Approved
02/22/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM00217, TI Dental Office
4850 E BROADWAY

The electrical plans have been denied for the following:

1. Sheet E2.0 , following circuits are on the panel schedule , cannot locate on power plan, Pnl A 14-16 , 29 , 31 , and 30-32.
2. To clarify , only one Dental Chair being provided with power ?
3. Sheet E1.0 , in rooms #117 and 118 , what does the homerun B-XX stand for ? Will these be future circuits ?
4. Commercial Submittal Requirements for TI's require Fault Current calc's at service and panels with new or up-graded services ,

Ray T Majuta
Elect Pln Ck, PDSD, City of Tucson
2/22/10.
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
02/23/2010 SUE REEVES REJECT SHELF Completed