Permit Number: T10CM00201
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00201
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2010 TERRY STEVENS ZONING REVIEW Approved
01/26/2010 LOREN MAKUS ENGINEERING REVIEW Approved
01/26/2010 ERIC NEWCOMB ADA REVIEW Passed
01/26/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET IA1.0: NO EGRESS IS ALLOWED THROUGH STORAGE AREAS PER IBC SECTION 1014.2(2).
2. GENERAL: A MINIMUM LETTERING HEIGHT OF 3/32" IS REQUIRED ON ALL DRAWINGS (SHEETS IA1.1 & IA3.0).
01/26/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
01/26/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
01/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations to take into account the different occupancy loads in the project space. Reference: Sections 403.3 and 403.3.2, IMC 2006.
01/27/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/27/2010 ROBERT SHERRY WATER REVIEW Approved
01/27/2010 MARTIN BROWN FIRE REVIEW Approved
01/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The branch piping size called out for the urinal flush valve will result in a water velocity greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Section A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
02/01/2010 GBONILL1 WWM REVIEW Needs Review