Permit Number: T10CM00149
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00149
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
01/20/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
01/20/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/20/2010 ERIC NEWCOMB ADA REVIEW Passed
01/20/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-000; TOILET ROOM DETAILS: REVISE SIDE WATER CLOSET CLEARANCES DETAIL.
2. GENERAL: PROVIDE INFORMATION ON THE DRAWINGS INDICATING HOW A MAXIMUM OF 20% OF THE PROJECT COST IS BEING USED FOR ACCESSIBILITY UPDATES.
01/21/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
01/21/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/21/2010 ROBERT SHERRY WATER REVIEW Approved
01/21/2010 STEVE SHIELDS ZONING REVIEW Approved
01/21/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: 5870 E Broadway Bl #416
T10CM00149


The Electrical Plans have been denied for the following:
1. City of Tucson TI submittals required to have 2006 IECC
Lighting Budget Calculations.

Ray T Majuta
Elect Pln Ck
PSDS, City of Tucson
1/21/10
Ray.Majuta@tucsonaz.gov
01/22/2010 MARTIN BROWN FIRE REVIEW Approved