Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00141
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 01/19/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 01/19/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 01/19/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/19/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 01/20/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/21/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/21/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a shutoff valve for the CW supply to the water heater. 2. Provide a vacuum relief valve for the elevated water heater. 3. The T&P relief shall not terminate into an elevated sink. 4. Revise the design of the water heater platform to coordinate with the architectural requirements. 5. Provide a pan under the water heater. |
| 01/21/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/21/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/26/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |