Permit Number: T10CM00137
Parcel: 133200570

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM00137
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2010 GERRY KOZIOL WWM REVIEW Approved
02/05/2010 JEFF DRUMM LANDFILL REVIEW Passed
02/18/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM0137

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007.

SITE PLAN:

1. Show compliance with the Pool Barrier requirement by including a 4' barrier between the addition (openings) door/windows and the pool, 2006 IRC Appendix G (Amendment).

STRUCTURAL PLANS:

1. Notate the requirement for 5/8" anchor bolts needed for the HD5 brace wall connections, R602.10.8.
2. Provide detail for bracing trusses at gable ends to prevent rotation and provide lateral stability, R802.10.3.
3. Specify and detail all over-framing connections for intersecting pitched roof assemblies. Provide a minimum opening of 22" by 30" for access and ventilation between existing and new attic areas (>30 S.F.) on the Roof Framing Plan, R807.

SECTIONS - DETAILS:

1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
2. The installation of a fiber glass shingle on roof surfaces over unvented attic space may void the manufacturer's warranty. Show compliance with R806 by providing tile, metal or built-up covering, or show the shingle manufacturer's requirement.

PLUMBING PLANS:

1. The fixture unit schedule shows the need for a 1-1/4" service pipe, IRC P2903.6. Show the existing water service pipe size and any replace sizes.

MECHANICAL PLANS:

1. Show a means of make-up air to the laundry closet (transfer grille, louvered or undercut door), M1307.

ELECTRICAL PLANS:

1. Show the location of each outlet on the Electrical Plan, E3305.1. Show circuit #1, 3 & 17.
2. Show overcurrent protection not exceeding the allowable conductor ampacity, E3605.5. Revise the breaker or wire size of circuit #5, 7.
3. Show or note a disconnect means or a locking breaker for the water heater, E4001.5.

OUTDOOR LIGHTING CODE

1. Provide spec sheets for all full cut-off fixtures showing the lamp type, placement and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style).

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review