Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00126
Parcel: 136221160

Address:
2654 S MARC DR

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM00126
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM00126
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Provide a system layout plan showing the location of system components in relation to structures and utilities. Clarify the inconsistent structural summary entries of Manufactured Truss and Post/beam without ceiling.
" Provide a line diagram identifying each component and circuit notating (conductor & protection) sizes and installation details (conductor insulation type).
" Show a DC grounding electrode conductor size equal to the neutral conductor and not smaller than #8 (copper), NEC 250.166.

STRUCTURAL PLANS:
1. Provide complete roof framing information for determining load carrying capacity of each structure supporting a collector group. Show size, spacing and span of all framing members including trusses, joists, rafters and beams, R301.1. Demonstrate the ability for supporting the existing and additional dead load along with a 20 PSF live load for field assembled structures, or show that each engineered truss receives no more than 200 pounds of additional dead loading, or provide an engineer's calculation, design and seal for verifying the truss load carrying capacity, M1401.
NOTES / SPECIFICATIONS
1. Provide the exact wording and location for the "Photovoltaic System Disconnect" marking required by NEC 690.14 (C) (2).
2. Provide the exact wording and location for the Warning Sign required by NEC 690.17.
3. Provide the exact wording and location for the DC Power Source "Imp, Vmp, Vmax, Isc" marking required by NEC 690.53.
4. Provide the exact wording and locations for any plaques which may be required for non co-located disconnects by NEC 690.56 (B).
5. Provide the location for the "backfed" circuit breaker in compliance with NEC 690.64 (B) (5).
6. Specify that the module interconnection connectors are capable of interrupting the circuit current without danger to the operator, or marked: "Do Not Open Under Load." (Reference NEC 690.33 (E) and Handbook commentary.)

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2010 DELMA ROBEY OUT TO CUSTOMER Completed
03/03/2010 SUE REEVES REJECT SHELF Completed