Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00124
Parcel: 12801007A

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T10CM00124
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The use of a double-check valve backflow preventer is not appropriate in this case; see Section 603.4.6.1, UPC 2006. In addition, if a backflow assembly is to be located above the ceiling, provide access as described in Section 603.3.4, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/01/2010 GERARDO BONILLA OUT TO CUSTOMER Completed