Permit Number: T10CM00124
Parcel: 12801007A

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T10CM00124
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The use of a double-check valve backflow preventer is not appropriate in this case; see Section 603.4.6.1, UPC 2006. In addition, if a backflow assembly is to be located above the ceiling, provide access as described in Section 603.3.4, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/01/2010 GERARDO BONILLA OUT TO CUSTOMER Completed