Permit Number: T10CM00124
Parcel: 12801007A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM00124
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide backflow protection for the misting system per Section 603.4.6, UPC 2006. The type of backflow protection to be installed will depend upon the design of the misting system; specify the type of backflow prevention device required. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
2. Clarify how the dirt leg and shutoff valve arrangement shown in detail P6.0-02 complies with the requirements of Section 1212.7, UPC 2006 (i.e. show the location of the gas inlet on the detail).
05/18/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
05/25/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2010 CPIERCE1 OUT TO CUSTOMER Completed
05/27/2010 CPIERCE1 REJECT SHELF Completed