Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T10CM00124
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/13/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide backflow protection for the misting system per Section 603.4.6, UPC 2006. The type of backflow protection to be installed will depend upon the design of the misting system; specify the type of backflow prevention device required. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. 2. Clarify how the dirt leg and shutoff valve arrangement shown in detail P6.0-02 complies with the requirements of Section 1212.7, UPC 2006 (i.e. show the location of the gas inlet on the detail). |
05/18/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/25/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/27/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
05/27/2010 | CPIERCE1 | REJECT SHELF | Completed |