Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00124
Parcel: 12801007A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM00124
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2010 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
04/09/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
04/09/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
04/12/2010 LAITH ALSHAMI ENGINEERING REVIEW Approved
04/12/2010 TERRY STEVENS ZONING REVIEW Approved
04/12/2010 DAVE MANN FIRE REVIEW Denied Please include the following fire sprinkler design criteria to the plans. THIS INFORMATION CANNOT BE DEFERRED; ONLY THE SHOP DRAWINGS AND CALCULATIONS.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 837-7030 or 837-7029
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
Also, please clearly indicate locations of panic hardware.
04/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T10CM00124, 5510 E Broadway Bl
B J'S Restaurant

The last item needed is corrected lay out for Electrical Room as discussed withh EE,on 4/14/10 by e-mail.

Ray T Majuta, Elect Pln Review,
PDSD, City of Tucson,
4/18/10
Ray.Majuta@tucsonaz.gov
04/23/2010 ROBERT SHERRY WATER REVIEW Approved
04/26/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief for WH-4. Reference: Section 608.7, UPC 2006.
2. Comment not resolved; each piece of equipment requiring backflow protection shall be independently protected. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection on the drawings. Reference: Sections 602.3, 603.0 (with local amendments), and Table 6-2, UPC 2006.
3. The floor drain FD-1, located near column C.5-2.5, appears to have a trap arm that exceeds the allowable length. Revise the trap arm length per Section 1002.2, UPC 2006.
04/26/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved. Revise the energy code analysis, using the correct climate zone (Pima County < 4,000 feet, not the town of Pima, Arizona). Revise the building design as required to meet the code requirements. Reference: Section 302.2, IECC 2006, as amended by the City of Tucson.
2. Comment not resolved. The roof is shown as having continuous insulation of R-19, not the R-30 shown on the calculations and no indication of the R-value for the exterior walls is shown on the drawings. Revise the energy code analysis, coordinating the building components used in the analysis with those shown on the drawing. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Section 502, IECC 2006, as amended by the City of Tucson.
3. Comment not addressed. Ventilation refers to the amount of outside air introduced into the building, not the air pressure balance. Provide calculations demonstrating adequate ventilation. See Section 403, IMC 2006 for information on the calculations required. Reference: Section 401.2, IMC 2006.
04/28/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2010 SUE REEVES OUT TO CUSTOMER Completed
04/28/2010 SUE REEVES REJECT SHELF Completed