Permit Number: T10CM00124
Parcel: 12801007A

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T10CM00124
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2010 ANDREW CONNOR LANDSCAPE REVIEW Approved
03/17/2010 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T10CM00124
5510 E. Broadway Blvd
Site Plan

TRANSMITTAL DATE: 03/18/10

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. DS 2-02.2.1.A.8 In the parking calculations clearly indicate that the building parked at a ratio of 1:400 is a retail - furniture store use.

2. DS 2-02.2.1.A. Provide detail of the class one locker and class two bicycle rack.

Provide 3' clearance at the front of the class two bicycle parking racks.

3. The proposed use should be list as "Food Services" on sheet C-1.

4. DS 2-02.2.1.A.12 Clarify the ramp adjacent to the trash enclosure.

5. The above comments are minor in nature and can be reviewed over the counter by setting an appointment with me.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T10CM00124-2.doc
03/24/2010 LAITH ALSHAMI ENGINEERING REVIEW Approved Laith Alshami, Engineering and Floodplain Review, 03/24/2010,

The submittal has been reviewed. The Drainage Statement is acceptable for Site Plan purposes and it is hereby approved. Additional drainage related information might be required with the grading plan. The Site Plan is recommended for approval pertaining to Engineering and Floodplain Review. Additional information and details (such as the trash enclosure detail) shall be provided on the grading plan.
03/25/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the site drawing to include the location and rim elevation of the next upstream sanitary manhole. Reference: City of Tucson Development Standard No. 2-01.1.0 2 3.8 D and Section 103.2.3, UPC 2006.
2. The site plan on sheet C3 shows the reduced pressure backflow prevention assembly that is to protect the municipal water supply located in the mechanical room of the building. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
04/01/2010 SUE REEVES REJECT SHELF Completed