Permit Number: T10CM00123
Parcel: 14117007Q

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00123
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2010 JASON GREEN ENGINEERING REVIEW Approved
01/20/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/20/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/20/2010 ERIC NEWCOMB ADA REVIEW Passed
01/20/2010 ROBERT SHERRY WATER REVIEW Approved
01/20/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
01/20/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water heater detail (3/P-1) to install the vacuum relief per its listing: "No valve is to be placed between the relief valve and the tank." Reference: Sections 310.4 and 608.7, UPC 2006.
2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported (nothing is shown on the architectural drawings). Reference: Sections 310.0 and 314.5, UPC 2006.
3. Show how the condensate drain is to terminate at the bottleless water dispenser. Reference: section 103.2.3, UPC 2006.
01/20/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
01/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/02/2010 TERRY STEVENS ZONING REVIEW Approved
02/03/2010 CPIERCE1 WWM REVIEW Needs Review
02/03/2010 MARTIN BROWN FIRE REVIEW Approved