Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00123
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
01/20/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/20/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
01/20/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/20/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
01/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water heater detail (3/P-1) to install the vacuum relief per its listing: "No valve is to be placed between the relief valve and the tank." Reference: Sections 310.4 and 608.7, UPC 2006. 2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported (nothing is shown on the architectural drawings). Reference: Sections 310.0 and 314.5, UPC 2006. 3. Show how the condensate drain is to terminate at the bottleless water dispenser. Reference: section 103.2.3, UPC 2006. |
01/20/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
01/21/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/02/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
02/03/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
02/03/2010 | MARTIN BROWN | FIRE | REVIEW | Approved |