Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00117
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2010 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/19/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/19/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/19/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/19/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/19/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 01/19/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/19/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 01/19/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/19/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 01/22/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/22/2010 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/22/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |