Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00109
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2010 | DAVID RIVERA | ZONING | REVIEW | Passed | |
| 01/19/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the termination of the restroom exhaust complies with the requirements of Section 401.4.2, IMC 2006 |
| 01/19/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T10CM00109, provide circuit for smoke detectors, to be of elect/battery type, unswitched. Ray T Majuta Elect Pln Ck 1/19/10 Ray.Majuta@tucsonaz.gov |
| 01/19/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location and sizes of the water meter and the backflow preventer. |
| 01/19/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/19/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 01/19/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide specifications for fixture P-5. 2. Provide a waste and vent riser diagram. 3. Clarify the key notes. |
| 01/19/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/19/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/19/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/19/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 01/26/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/26/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |