Permit Number: T10CM00109
Parcel: 121030630

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00109
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2010 DAVID RIVERA ZONING REVIEW Passed
01/19/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the termination of the restroom exhaust complies with the requirements of Section 401.4.2, IMC 2006
01/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T10CM00109, provide circuit for smoke detectors, to be of elect/battery type, unswitched.

Ray T Majuta
Elect Pln Ck
1/19/10
Ray.Majuta@tucsonaz.gov
01/19/2010 ROBERT SHERRY WATER REVIEW Denied Show the location and sizes of the water meter and the backflow preventer.
01/19/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/19/2010 PAUL MACHADO ENGINEERING REVIEW Approved
01/19/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications for fixture P-5.
2. Provide a waste and vent riser diagram.
3. Clarify the key notes.
01/19/2010 MARTIN BROWN FIRE REVIEW Approved
01/19/2010 ERIC NEWCOMB ADA REVIEW Passed
01/19/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/19/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
01/26/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2010 SUE REEVES OUT TO CUSTOMER Completed