Permit Number: T10CM00101
Parcel: 10705126B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM00101
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2010 LOREN MAKUS ENGINEERING REVIEW Approved
01/22/2010 MARTIN BROWN FIRE REVIEW Approved
01/27/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET SGN; FOUNDATIONS: NOTE 4 INDICATES A SOIL REPORT WAS USED IN DETERMINING THE ALLOWABLE SOIL PRESSURE. PROVIDE THE REPORT FOR REVIEW. SHEET S-1 NOTES INDICATE THE SOIL BEARING PER IBC. COORDINATE.
2. SHEET S-1 (FOOTING SCHEDULE); STRUCTURAL CALCULATIONS (PAGE 14): THE CALCULATIONS INDICATE 4-#5 REBAR EACH WAY IN THE GARAGE DOOR FOOTINGS, WHILE THE SCHEDULE INDICATES 3-#5 EACH WAY. CLARIFY.
3. SHEET D-1; DETAIL 6: THE SECTION AND ELEVATION INDICATE STIRRUPS AS SHOWN IN THE SCHEDULE. NO SCHEDULE IS PROVIDED. INCLUDE STIRRUP INFORMATION ON THE SECTION.
4. SHEET D-1; DETAIL 6: THE SECTION INDICATES THE TOP REINFORCING WHERE SHOWN IN SCHEDULE. NO SCHEDULE IS PROVIDED. INCLUDE THE TOP REINFORCING INFORMATION ON THE SECTION, OR REMOVE IF NOT REQUIRED (PER THE STRUCTURAL CALCULATIONS).
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/27/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
01/29/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM00101, 801 W Miracle Mile
Gragages (15) for Buildings

The electrical plans have been denied for the following:

1. Provide a cut sheet of the fixtures to be used as required per Submittal Requirements.
2. The Outdoor Light Ordinance requires the calculation for lumen compliance be for the entire site not just the building area for the garages, The existing approved outdoor lighting budget for the buildings and area around them is also inclusive.

Ray T Majuta,PSDS, City of Tucson,
Elect Plan Ck,
1/30/10,
Ray.Majuta@tucsonaz.gov
02/04/2010 DAVID RIVERA ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/08/2010 SUE REEVES OUT TO CUSTOMER Completed
02/08/2010 SUE REEVES REJECT SHELF Completed