Permit Number: T10CM00093
Parcel: 117110170

Address:
177 N CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00093
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2010 TERRY STEVENS ZONING REVIEW Approved
01/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the type and design mass of the refrigerant for the chillers.
2. Provide calculations for the normal and emergency exhaust flow rates. Reference: Section 1105, IMC 2006.
01/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/14/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
01/14/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/14/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
01/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/14/2010 ERIC NEWCOMB ADA REVIEW Passed
01/14/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/14/2010 PAUL MACHADO ENGINEERING REVIEW Approved
01/14/2010 MARTIN BROWN FIRE REVIEW Approved
01/14/2010 ROBERT SHERRY WATER REVIEW Approved