Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T10CM00067
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/08/2010 | RONALD BROWN | BUILDING-RESIDENTIAL | REVIEW | Denied | SITE PLAN: 1. Location of utility lines and meters from property line to building, R106.1.1. 2. Please show overhead or underground electrical service. FLOOR PLANS: 3. Identify ceiling heights in all areas. Note average height at sloped ceiling areas, R305.1. 4. Show the location of attic access min. 22"x30", R807. FOUNDATION PLANS: 5. Provide a note for termite treatment, R320 as amended. 6. Note grade away from foundations shall fall min 6” within the first 10’, R401.3. 7. Please provide a completed Special Inspection Certifications for appproval. These should include as a minimum: Concrete and Field Welding. ELEVATIONS: 8. Provide an attic space ventilation calculation and note the size and location of all attic vents needed to comply, R806.2. SECTIONS - DETAILS: 9. Welded connections require special inspections. If used, a special inspection request must be included with the permit application, UAC306.1.5. 10. Detail all over-framing connections for intersecting pitched roof assemblies. Provide a minimum opening of 22" by 30" for access and ventilation between over-framed assemblies (>30 S.F.), R807. ELECTRICAL PLANS: 11. Electrical work shall comply with 2006 IRC, chapt 33-42. 12. Provide equipment rated for 22,000 AIC short circuit protection when the underground cable length is less than 45 feet, 2006 Electric Service Requirements TEP SR-510. 13. Lights installed over a shower or bathtub must be approved for use in wet area, E3903.8. 14. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11. 15. Exterior outlets at grade level shall be provided at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3. PLUMBING PLANS: 16. Plumbing shall comply with 2006 UPC with state amendments (AZ State plumbing code). The plans should reference this code, or appeal to the Building Official for alternate design approval. Your plumbingh notes on sheet MP refers to the IRC while the front covber sheet refers to the 2006 UPC. Please clarify. 17. Fixture unit schedule required for the entire property (including existing) UPC Tables 6-5 and 7-3. 18. Provide the maximum developed length of water line from the meter the furthest appliance served, and the diameter of the water line, UPC Table 6-6. 19. Condensate disposal may not discharge into a plumbing vent, UPC 908.1. 20. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, UPC 1217.0 Table 12-8. Please show comparision of the old unit to the new unit and any changes required such as increased comsumption. MECHANICAL PLANS: 21. Show supply and return ducts with minimum R-8 insulation, R1103.2.1. 22. Show the condensate line and secondary for HVAC unit, M1411.3. OUTDOOR LIGHTING CODE 23. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. 24. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). INTERNATIONAL ENERGY CONSERVATION CODE: 25. Provide a note requiring the insulation certificate shall be posted in the electrical distribution panel before final inspection, N1101.8. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/13/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/13/2010 | SUE REEVES | REJECT SHELF | Completed |