Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM00063
Parcel: 12703559C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00063
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2010 DAVE MANN FIRE REVIEW Approved
01/14/2010 PAUL MACHADO ENGINEERING REVIEW Approved
01/14/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
01/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: T10CM00063
5515 E 5th St, OFFICE


The electrical plans for this project denied for the following,

1. The feeders from the CT can show 8 #3/0's and 2 # 6 grd's. The grounds must be sized per 2005 NEC 250-66 since the is no overcurrent device ahead of this feeder. Now they appear to be sized per 250-122.
2. Circuits A-2 and 4 are reversed per panel and power plan.
3. Provide a time clock for exhaust fan in restroom as required for exhaust to come on during work hrs, or other means.

Ray T Majuta
Elect Pln CK
PSDS, c of t.
1/20/10
520/837/4988
01/20/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/20/2010 RONALD BROWN ZONING HC REVIEW Approved
01/20/2010 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
01/21/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/21/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/21/2010 ROBERT SHERRY WATER REVIEW Approved
01/21/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/21/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2010 DELMA ROBEY OUT TO CUSTOMER Completed