Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00041
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise water heater detail to show the vacuum relief valve located on the cold wate inlet, between the shut off valve and the water heater, per its listing. 2. An indirect waste receptor shall not be located in a restroom. Reference: Section 804.1, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |