Permit Number: T10CM00041
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM00041
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/09/2010 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
02/09/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/09/2010 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. Each fixture trap requires a vent. Reference: 901.0 2006 UPC. see sheet P100 floor drains. 2. A water heater located above the fixture outlets requires a vacuum relief valve. Reference: 608.7 2006 UPC. 3. Show the location of the piping, and the routing to the mop sink as described in the water heater detail on P100.
02/10/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
02/11/2010 SUE REEVES REJECT SHELF Completed