Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00041
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/09/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/09/2010 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
02/09/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/09/2010 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Each fixture trap requires a vent. Reference: 901.0 2006 UPC. see sheet P100 floor drains. 2. A water heater located above the fixture outlets requires a vacuum relief valve. Reference: 608.7 2006 UPC. 3. Show the location of the piping, and the routing to the mop sink as described in the water heater detail on P100. |
02/10/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/11/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
02/11/2010 | SUE REEVES | REJECT SHELF | Completed |