Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM00041
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
01/08/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that recirculation of the air from the restroom will not occur (i.e. the restroom fans shall operate whenever the HVAC system is supplying air to the restrooms). Reference: Section 403.2.1, IMC 2006. |
01/08/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | Too large for walk-thru review, submit for review. Ray T Majuta Elect Pln Ck PDSD<City of Tucson Ray.Majuta@tucsonaz.gov |
01/08/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/08/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
01/08/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | |
01/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. |
01/08/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
01/08/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/08/2010 | ERIC NEWCOMB | ADA | REVIEW | Approved | |
01/08/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/08/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Needs Review |