Permit Number: T10CM00041
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00041
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2010 STEVE SHIELDS ZONING REVIEW Approved
01/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that recirculation of the air from the restroom will not occur (i.e. the restroom fans shall operate whenever the HVAC system is supplying air to the restrooms). Reference: Section 403.2.1, IMC 2006.
01/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review Too large for walk-thru review, submit for review.

Ray T Majuta
Elect Pln Ck
PDSD<City of Tucson
Ray.Majuta@tucsonaz.gov
01/08/2010 ROBERT SHERRY WATER REVIEW Approved
01/08/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
01/08/2010 CPIERCE1 WWM REVIEW Needs Review
01/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
01/08/2010 JASON GREEN ENGINEERING REVIEW Approved
01/08/2010 MARTIN BROWN FIRE REVIEW Approved
01/08/2010 ERIC NEWCOMB ADA REVIEW Approved
01/08/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/08/2010 ERIC NEWCOMB ZONING HC REVIEW Needs Review