Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM00028
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. NOT USED 2. CODE INFORMATION: a. The accessibility requirements of the 2006 IBC are clearly defined under Chapter 11 and the ICC (ANSI) 117.1. An ADAAG accessibility review is an owner option and may be obtained by filing an appeal with the building official. The appeal form is available on our web site. Please submit appeal in care of Mr. LeeRay Hanley. A $120.00 fee is applicable for all appeals. b. The occupant load for Mercantile are as per 2006 IBC, Table 1004.1.1. Please recalculate load as per these requirements. DETAIL 1/A2.01 3. Please provide a blow up plan of the EWC nitch showing all dimensions including accessible clearance dimensions as per ICC (ANSI) 117.1, Section 602.2. 4. The men and women toilet room nos. 104 and 105 are not code compliant. Reference comment 5 below. SHEET 4.01 5. Detail 1: Please provide a clear floor space for the men's and women's water closets as per ICC (ANSI) 117.1, Section 604.3. The lavatory may not encroach this clearance requirement. 6. Details 12 and 13: Show vertical grab bar as required by ICC (ANSI) 117.1, Section 604.3 7.In general, delete all note references to ADA guidelines and reference all accessible guidelines to the 2006 IBC, Chapter 11 and ICC (ANSI) 117.1. DETAIL 5c/A5.01 6. Provide laterial bracing as required by 2006 IBC, Section 1607.13 MECHANICAL AND ELECTRICAL SHEETS 7. The minimum sized lettering for all sheets is 3/32". Please revise all mech and elect sheets to meet this requirement. 8. Please provide a water heater structural support detail and structural calculations. END OF REVIEW |
| 01/12/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | Reference Building - Commerical folder for comments |
| 01/13/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM00028, 4500 N Oracle #363 TI Retail, The electrical plans for this project have been denied for the following: 1. As per Commercial Submittal Requirements, plans must be drawn to a minimum text size of 3/32'' all uppercase. 2. As per Commercial Submittal Requirements, provide 2006 IECC light Budget calculations and indicate required switching per IECC. 3. Some lighting circuits appear to have more that the indicated loads as per panel schedule. 4. Provide written confirmation from Mall Management on allowed power for this space. Ray T Majuta Elect Pln Ck, PDSD, City of Tucson, 1/19/10 Ray.Majuta@tucsonaz.gov |