Permit Number: T10CM00028
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00028
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
01/06/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/06/2010 ERIC NEWCOMB ADA REVIEW Passed
01/06/2010 ROBERT SHERRY WATER REVIEW Approved
01/06/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/06/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the proposed water heater platform is to be connected to the building structure. Reference: Section 314.5, UPC 2006.
2. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
3. An indirect waste receptor shall not be located in a restroom. In addition, the termination of a temperature and pressure relief from a water heater over a floor drain may cause splashing or flooding. Reference: Sections 608.5 and 804.1, UPC 2006.
4. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006.
5. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
01/06/2010 ERIC NEWCOMB ZONING HC REVIEW Needs Review
01/07/2010 CPIERCE1 WWM REVIEW Needs Review
01/07/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
01/07/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
01/07/2010 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/07/2010 MARTIN BROWN FIRE REVIEW Approved