Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM00011
Parcel: 12510003G

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T10CM00011
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2010 ROBERT SHERRY WATER REVIEW Approved
02/09/2010 DAVE MANN FIRE REVIEW Denied Fire Comments

Sheet A 4.
If the end units are A2 occupancies the rear doors 1 and 4 require panic hardware.

Sheet MP1.0
Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
02/09/2010 RONALD BROWN ZONING HC REVIEW Passed Completed by Third Party reference comments from Stantec.
02/09/2010 GERRY KOZIOL WWM REVIEW Denied need wastewater IWC review for future grease interceptor adequacy, sampling locations, etc. Tom Tomchak, 5025 W Ina Rd - 443-6200
need manhole construction permit review & approval for 6" HCS- 3rd floor PCRWRD/ Roy Montoya 740-6357
02/12/2010 CPIERCE1 ZONING REVIEW Needs Review
02/12/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2010 CPIERCE1 OUT TO CUSTOMER Completed