Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T10CM00011
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/08/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/09/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments Sheet A 4. If the end units are A2 occupancies the rear doors 1 and 4 require panic hardware. Sheet MP1.0 Please include the following fire sprinkler design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. |
02/09/2010 | RONALD BROWN | ZONING HC | REVIEW | Passed | Completed by Third Party reference comments from Stantec. |
02/09/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | need wastewater IWC review for future grease interceptor adequacy, sampling locations, etc. Tom Tomchak, 5025 W Ina Rd - 443-6200 need manhole construction permit review & approval for 6" HCS- 3rd floor PCRWRD/ Roy Montoya 740-6357 |
02/12/2010 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
02/12/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/12/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |