Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM00008
Parcel: 12405142A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T10CM00008
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
03/03/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
03/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show the location of the visual and audible alarms for the sump pump Reference: Section 710.9, UPC 2006.
03/03/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved. The exhaust from the restroom on the lower level (EF-3) appears to terminate in a below-grade area near an exit door and below a walkway or awning. Clarify how this conforms to the requirements of Section 401.4.1, IMC 2006.
2. Provide an electrical design to show how the exhaust fans are to be interconnected to the A/C units. Reference: Section 403.2.1, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/05/2010 DELMA ROBEY OUT TO CUSTOMER Completed
03/05/2010 SUE REEVES REJECT SHELF Completed