Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM00008
Parcel: 12405142A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM00008
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2010 DAVE MANN FIRE REVIEW Approved
01/07/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A4.1; ELEVATION 1: THE SINK SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.3 AND ANSI 804.4.
2. SHEET A4.1; ELEVATION 1: THE COUNTERS AND WORK SURFACES SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.11 AND ANSI 804.3.
3. SHEET A4.1; ELEVATION 5: THE SINK SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.3 AND ANSI 804.4.
4. SHEET A4.1; ELEVATION 5: THE COUNTERS AND WORK SURFACES SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.11 AND ANSI 804.3.
5. SHEET A4.1; ELEVATION 7: THE SINK SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.3 AND ANSI 804.4.
6. SHEET A4.1; ELEVATION 7: THE COUNTERS AND WORK SURFACES SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.11 AND ANSI 804.3.
7. SHEET A4.1; ELEVATION 8: THE SINK SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.3 AND ANSI 804.4.
8. SHEET A4.2; ELEVATION 1: THE COUNTERS AND WORK SURFACES SHALL MEET THE REQUIREMENTS FOR ACCESSIBILITY PER THE IBC SECTION 1109.11 AND ANSI 804.3.
9. GENERAL: CLARIFY THE EXISTING CONDITION ON THE SOUTH WALL AT THE UPPER LEVEL. DOES THE NEW DOOR OPEN ONTO AN EXTERIOR WALKWAY? PROVIDE AN EXTERIOR ELEVATION OF THIS WALL.
10. GENERAL: PROVIDE NORTH/SOUTH AND EAST/WEST BUILDING SECTIONS. THE BUILDING FOOTPRINT IS NOT ENTIRELY CLEAR FROM THE PLANS.
11. GENERAL: A MINIMUM LETTERING HEIGHT OF 3/32" IS REQUIRED ON ALL DRAWINGS (SEE SHEET A5.2).
12. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS.
01/11/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
01/12/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The exhaust from the restroom on the lower level (EF-3) appears to terminate in a below-grade area near an exit door and below a walkway or awning. Clarify how this conforms to the requirements of Section 401.4.1, IMC 2006.
2. Provide information on the sequence of operation for the restroom exhaust fans to show that recirculation of the air from the restrooms will not occur (i.e. the restroom fan shall operate whenever supply air is introduced into the restroom). Reference: Section 403.2.1, IMC 2006.
01/12/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include the cleanout shown in detail 5/P3.1 on the plumbing floor plan (P2.1 and the waste and vent schematic on P3.3. Reference: Section 103.2.3, UPC 2006.
2. Clarify the location of the water heater; on the water schematic (P3.3), it appears to be located on the upper floor. Reference: Section 103.2.3, UPC 2006.
3. Clarify why slopes of 1/8" per foot will be required for the new 4" drainage pipes. Reference: Section 708.0, UPC 2006.
4. Verify that sump pump controls (e.g. visual and audible alarms, etc.) per Section 710.9, UPC 2006 have been provided.
5. Indicate the size, route, and termination of the vent for the sump. Reference: Section 710.10 and Table 7-5, UPC 2006.
01/12/2010 ROBERT SHERRY WATER REVIEW Approved
01/12/2010 MICHAEL ST. PAUL ZONING REVIEW Denied A site plan is required. The proposed use as medical outpatient constitutes a change of use.

This appears to be a full code compliance due to a increase in parking. The last approved use is for retail. Please be aware that there is a variance for the last approved use on this site (C10-96-10).
01/14/2010 GERRY KOZIOL WWM REVIEW Approved
02/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
03/03/2010 SUE REEVES REJECT SHELF Completed