Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10BU01746
Parcel: 211350170

Review Status: Completed

Review Details: GRADING

Permit Number - T10BU01746
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2010 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: December 1, 2010
TO: Peter Abraham, P.E., Tucson Water, 310 West Alameda, Tucson Arizona 85747
SUBJECT: Tucson Water Southern Avra Valley Storage And Recovery Project (SAVSARP) Phase 1 Well SA-011A Engineering Review
ADDRESS: 2830 S Sandario Rd, north of Snyder Hill Road
LOCATION: T14S, R11E, Section 28
REVIEWER: Elizabeth Leibold, P.E.
FLOODPLAIN INFO: FIRM Panel: 040192200K (effective date 2/8/99), SFHA zone: A01. (Prelim map 2240L/AO1)
ACTIVITY NUMBERS: T10BU01746 / T10OT02519

SUMMARY: PDSD Engineering Division has reviewed the plan set submittal for Floodplain Use Permit and Grading Plan review, and recommends approval of the floodplain use permit and grading permit. The drainage report was reviewed for the phase 1 of the Tucson Water SAVSARP Well SA-011A only.

GRADING PERMIT CONDITIONS:
1) Admin.Dir.1.07-6.III.A: The following conditions apply to grading permit T10BU01746:
a) This permit is for the initial phase of the Tucson Water SAVSARP well improvements SA-011A phase 1 only.
b) The Southern Avra Valley Storage And Recovery Project (SAVSARP) Well SA-011A Phase 1 plans - Tucson Water Plan No.1-016-2010 (SA-011A) and specifications are a part of the grading permit. See also Floodplain Analysis Summary Report for Southern Avra Valley Storage and Recovery Project (SAVSARP) Planned Recovery-Well Pad Sites by TetraTech dated December 9, 2009, sealed 12/09/09 Michael Zeller, P.E.
c) Minimum pad elevation and well structure shall be set above the jurisdictional water surface to the elevation, as shown on the approved plans and drainage report, and shall be certified by an RLS.
d) Submit completed elevation certificates to City of Tucson Planning & Development Services Department Engineering Division for acceptance. For SAVSARP Well SA-011A, submit first elevation certificate after compaction and completion of the fill pad, indicating minimum pad grade of 2300.57, and final elevation certificate indicating minimum elevation of top of well casing set at 2302.57.
e) Submit a copy of the as-builts to City of Tucson Planning & Development Services Department upon completion.
2) DS Sec.10-02.2.3.1.2.F: All conditions of Pima County Regional Flood Control District Floodplain Use Permit No.10-010 approved 2/16/10 shall apply.
3) DS Sec.11-01.4.1.C: Additional grading and floodplain review by the City of Tucson Planning & Development Services Department will be required for permits for the future structures or other future phase improvements on the constructed pad. At the time when permits are required for the future control building, submit copy of final elevation certificate with plans and drainage statement.

If you have any questions, call me at 837-4934.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
12/06/2010 MICHAEL ST. PAUL ZONING REVIEW Passed
12/21/2010 ANDREW CONNOR NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2011 SUE REEVES APPROVAL SHELF Completed
01/06/2011 CINDY AGUILAR OUT TO CUSTOMER Completed