Permit Number: T10BU01511
Parcel: 13214078H

Address:
1025 E AJO WY

Review Status: Completed

Review Details: TANKS

Permit Number - T10BU01511
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2010 DAVE MANN FIRE REVIEW Approved
10/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied All electrical work to be installed in a hazardoud area to be sealed by an EE,as per Commercial Submittal Requirements per City of Tucson.

Ray T Majuta,Elect Pln Ck,
PDSD,City of Tucson,
10/21/10,
Ray.Majuta@tucsonaz.gov
10/26/2010 DAVID RIVERA ZONING REVIEW Denied The site plan has not ben approved as of this review for the fuel tanks. Zoning will re-review the plan on the next submittal to ensure compliance with the approved site plan. Include a copy of the approved and stamped site plan with the next submittal unless the site plan is approved and scanned into SIRE where the plan can viewed by staff as reference.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2011 CPIERCE1 OUT TO CUSTOMER Completed