Permit Number: T10BU01433
Parcel: 116094370

Review Status: Completed

Review Details: GRADING

Permit Number - T10BU01433
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2010 ANDREW CONNOR NPPO REVIEW Denied NPPO pre permit inspection is required prior to grading inspection can be scheduled by calling IVR system and entering inspection code 09015 or calling Landscape Field Representative directly @ 837-4950

Grubbing, grading, and clearing are to occur only within the areas identified on the grading plan and staked on the site or lot. The limits should include all cut and fill areas, leach fields, septic tanks and future development areas identified

The portions of the site or lot to be left ungraded are to remain undisturbed and are not to be used for stockpiling of materials or excess fill, construction vehicle access, storage of vehicles during construction, or similar uses.

Include the location, size, color, and textural treatment of all retaining walls, riprapped slopes, or other constructed means of slope stabilization must be shown on one (1) of the plans submitted. Vegetation retention and re-vegetation should be used in conjunction with riprapping.

Ensure that all engineering comments are addressed.
09/27/2010 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T10CM02581 (T10BU01433 Grading)
3594 West Starr Pass Estates Court
New SFR


TRANSMITTAL: September 27, 2010


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


This site is located in the SR Zone (LUC Section 2.2.4). The Development Designator is "C" (LUC Section 2.2.4.2.A.1) and the Perimeter Yard Indicator is BB (LUC Sections 3.2.3.1.A and 3.2.6.4).

Provide all the site plan information on the site plan sheet as shown on the plot plan instruction/model. The lot coverage calculations are not required in this zone. Provide the address, the zone and the zoning of the adjacent lots.

Clearly depict the access easement along the north property line and remove any encroachment within the easement.

The Grading Plan must be approved for site plan approval.

Please be aware that additional comments may be necessary relative to information provided with subsequent submittals.
09/27/2010 LOREN MAKUS ENGINEERING REVIEW Denied September 28, 2010

T10BU01433 - Grading
T10CM02581 - Plot Plan

Please address the following comments:

1. The proposed driveway as shown requires cuts of as much as 20 feet. In order to stay within the proposed grading limits, the cut slopes will be nearly vertical. Provide a geotechnical report to identify any special requirements for this cut.
2. Include the cut and fill volume for the driveway in the cut and fill quantities.
3. The geotechnical report should address the preparation of the slope for acceptance of the fill, including benching.
4. Provide an interceptor swale around the up-hill side of the house to divert stormwater around the house.
5. For each of the retaining walls, provide representative grades at each side of the wall.
6. Provide cross section details for the project. Provide one representative east/west section and one representative north/south section as well as a section of the driveway showing uphill and downhill slope treatment.
7. The detail for the retaining wall adjacent to the pool is labeled "not to be used for swimming pool." Revise the plan to provide a structural wall adjacent to the pool or indicate that the wall in this area will be by separate permit and separate design.
8. Clearly indicate that there will be no development in the access easement or provide written concurrence from the beneficiaries of the easement for the encroachment.

If you have any questions, please contact me at loren.makus@tucsonaz.gov or 520.837.4927.

Loren Makus, EIT
Senior Engineering Associate

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2010 CPIERCE1 OUT TO CUSTOMER Completed