Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10BU01343
Parcel: 11615088L

Review Status: Completed

Review Details: WALLS SUBMITTAL

Permit Number - T10BU01343
Review Name: WALLS SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2010 ELIZABETH EBERBACH ENGINEERING REVIEW Denied DATE: September 10, 2010
TO: MPE/Swaim Assoc., Mark Bollard, RA
SUBJECT: 1601 West St Marys Rd, Generator enclosure north of hospital building
LOCATION: T14S R13E Sec10, Ward 1
FLOOD INFO: Zone A, 2210K
REVIEWER: Elizabeth Leibold, PE
ACTIVITY: T10OT01836 (Floodplain Use Permit), T10BU01343

SUMMARY:
The generator enclosure review plans were received and reviewed by Engineering Division. The subject project is adjacent to a critical facility hospital located within a Special Flood Hazard Area (SFHA) Zone A as shown on the Flood Insurance Rate Map (FIRM), Community- Panel No. 04019C-2210K, effective date February 8, 1999. Engineering Division of Development Services Department does not recommend approval of the plans until the following comments are addressed.

FLOODPLAIN USE PERMIT COMMENTS:
1) Tucson Code Sec.26-11.2(b)(5)b: Either provide one of the following:
a) Submit a drainage report indicating base flood depth and regulatory flood elevation for elevated pad for generator and any other proposed utility units; or
b) Show on the plan sheet xa1.1 pad elevation 2-ft above exiting grade for the proposed generator pad and any other proposed utility units (RFE NAVD88 = 2353.00).
2) Tucson Code Sec.26-11.2(h): An elevation certificate will be required and a preliminary document prepared by the City of Tucson will be provided at permit issuance. An Arizona registered land surveyor will be required to fill out the elevation certificate for the pad elevation prior to placing the generator, and submitted to PDSD for review. If the elevation certificate does not show sufficient elevation, the pad will need to be reconstructed for compliance.
3) DS Sec.2-02.2.1.A.16: Wall openings are indicated on the northeast corner of the wall enclosure. Clarify / provide additional wall openings on the west side of the wall structure for flood waters to flow into and through the enclosure area around the concrete pad.

Resubmit plan package with, or without, drainage report as described above. Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval. I can be reached at 837-4934 if you have questions.

Elizabeth Leibold, PE, CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/22/2010 SUE REEVES REJECT SHELF Completed