Permit Review Detail
Review Status: Completed
Review Details: MECHANICAL
Permit Number - T10BU01286
Review Name: MECHANICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the grease duct size to provide a minimum velocity of 1500 FPM. 2. Provide a non-combustible, cleanable, and grease resistant layer behind the hood. |