Review Details: MECHANICAL

Permit Number - T10BU01286
Review Name: MECHANICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the grease duct size to provide a minimum velocity of 1500 FPM.
2. Provide a non-combustible, cleanable, and grease resistant layer behind the hood.