Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10BU00313
Parcel: 117021360

Address:
27 W SPEEDWAY BL

Review Status: Completed

Review Details: BILLBOARD-BLDG

Permit Number - T10BU00313
Review Name: BILLBOARD-BLDG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. EXHIBIT 1 OF THE STIPULATION INDICATES THE BILLBOARD WITH COT ID#46 AT 27 W. SPEEDWAY BLVD. HAS ONLY ONE FACE, WHILE THE FIRST SHEET OF THE DRAWINGS (NOTE #5) INDICATES 2 FACES. THE SECOND SHEET INDICATES ONE FACE ONLY (EAST). CLARIFY.
03/22/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied COMMENTS ON AUTHORIZED REPAIR SUBMITTAL FOR CLEAR CHANNEL BILLBOARD COT ID
#46 AT 27 WEST SPEEDWAY BOULEVARD

Billboard Modification Site Plan

1. Correct east-west dimensions on aerial photograph overlay: the sum of
the dimensions need to add up correctly; the 10-foot width of the billboard
is excessive (actual width closer to 4 feet); the 6.5-foot distance to east
property line is insufficient (actual distance closer to 11 feet); also
correct "Alley" to "Ash Avenue".

Authorized Repair Plan (Drawing No.45-2072)

1. Amend note on plan that reads "No parts or components are to be removed,
installed, replaced and reinstalled" to read "No parts or components are to
be removed, installed, replaced or reinstalled" (i.e., change the "and" to
"or").
2. Plan View: provide separate detail indicating material and dimensions of
panel section clip.
3. Stringer/Face Mounting or Poster Panel Side View: provide the total
number of existing panel clips to be removed and reinstalled per face and
indicate which stringers the clips are fastened to.
4. Poster Panel Top View: delete second face depicted ("Back")
5. Add "Sheet 2 of 2" at appropriate location in or near the title block.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/02/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
11/02/2010 SUE REEVES REJECT SHELF Completed