Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T10BU00293
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 04/23/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10BU00293, 3960 N Sun Tran Bl New Fuel Tank and Associated Equipmt Electrical denied for the following: 1. What are the loads on Pnl MP-2, which allow this new fuel pump as added load. Provide the panel schedule with this plan. 2. Circuit FP-2 by the new Veeder Root Detection System, is this for the Veeder Root Detection Systen it self ? What type of a load are you talking about ? 3. Provide some info on the Detection System, how will this provide an alarm notice ? Ray T Majuta, Elect Pln Ck, PDSD, C of Tuc 4/24/10 Ray.Majuta@tucsonaz.gov |
| 04/26/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments Provide valuation for fuel tank part of project. Tank, piping pumps, etc. Sheet G0.006 The fire code is the 2006 IFC with amendments. Sheet PP1.6.1 The plans show 5 foot bollard spacing; IFC Section 312 requires 4 ft on center. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/29/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 04/29/2010 | CPIERCE1 | REJECT SHELF | Completed |