03/26/2010 DAVE MANN FIRE REVIEW Denied Fire Comments

Provide valuation for fuel tank part of project. Tank, piping pumps, etc.

Sheet G0.006

The fire code is the 2006 IFC with amendments.

Sheet PP1.6.1

The plans show 5 foot bollard spacing; IFC Section 312 requires 4 ft on center.