Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T10BU00293
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/26/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments Provide valuation for fuel tank part of project. Tank, piping pumps, etc. Sheet G0.006 The fire code is the 2006 IFC with amendments. Sheet PP1.6.1 The plans show 5 foot bollard spacing; IFC Section 312 requires 4 ft on center. |
| 03/30/2010 | SREEVES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 03/30/2010 | SREEVES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/30/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |