Permit Number: T10BU00288
Parcel: 99999999B

Address:
507 N 4TH AV

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T10BU00288
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
02/03/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair resubmittal for COT ID# 516 at
507 North 4th Avenue (T10BU00288).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. The resubmital needs to be under a registered engineer's stamp (as per
Exhibit 12, Sec. 1(b)(4) of the Stipulation).
2. A date key for the revisions needs to be provided.
3. The resubmittal is not fully responsive to Comment #2 on the original
submittal. Full dimensions need to be provided for the panel clip detail,
not just the outer dimensions.
4. The resubmittal is not responsive to Comment #3 on the original
submittal. More clearly specify the number of panel clips; four runs of nine
clips is the installation (36 total, rather than the 50 +/- stated).
5. Delete the reference to "actual size" on the panel clip detail (such
size is not accurate for reproductions at anything other than 100%).

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2011 DELMA ROBEY OUT TO CUSTOMER Completed
02/11/2011 SUE REEVES REJECT SHELF Completed