Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/13/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/03/2011 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments on the authorized repair resubmittal for COT ID# 516 at 507 North 4th Avenue (T10BU00288). Sheet 1 of 2 No comments. Sheet 2 of 2 1. The resubmital needs to be under a registered engineer's stamp (as per Exhibit 12, Sec. 1(b)(4) of the Stipulation). 2. A date key for the revisions needs to be provided. 3. The resubmittal is not fully responsive to Comment #2 on the original submittal. Full dimensions need to be provided for the panel clip detail, not just the outer dimensions. 4. The resubmittal is not responsive to Comment #3 on the original submittal. More clearly specify the number of panel clips; four runs of nine clips is the installation (36 total, rather than the 50 +/- stated). 5. Delete the reference to "actual size" on the panel clip detail (such size is not accurate for reproductions at anything other than 100%). |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/11/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
02/11/2011 | SUE REEVES | REJECT SHELF | Completed |