Review Details: BILLBOARD-BLDG
Permit Number - T10BU00288
Review Name: BILLBOARD-BLDG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/24/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Billboard Modification Site Plan 1. Indicate that Sheet 2 is not part of the submittal; alternatively, add "Sheet 2 of 2" on the Authorized Repair plan sheet. Authorized Repair Plan (Drawing No.45-2076) 1. Amend note on plan that reads "No parts or components are to be removed, installed, replaced and reinstalled" to read "No parts or components are to be removed, installed, replaced or reinstalled" (i.e., change the "and" to "or"). 2. Plan View: provide separate detail indicating material and dimensions of panel section clip. 3. Stringer/Face Mounting; Poster Panel Side View: provide the total number of existing panel clips to be removed and reinstalled per face and indicate which stringers the clips are fastened to. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 01/12/2011 | SUE REEVES | REJECT SHELF | Completed |