Permit Number - T10BU00287
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/07/2011 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Below are comments on the authorized repair resubmittal for COT ID# 144 at 1863 West Ajo Way (T10BU00287). Sheet 1 of 2 No comments. Sheet 2 of 2 1. The resubmittal needs to be under a registered engineer's stamp (as per Exhibit 12, Sec. 1(b)(4) of the Stipulation). 2. Add a date key for the revisions. 3. The resubmittal is not fully responsive to Comment #3 on the original submittal. Full dimensions need to be provided for the panel clip detail, not just the outer dimensions. 4. The resubmittal is not responsive to Comment #4 on the original submittal. More clearly specify the number of panel clips (the existing installation is 19 per face, consisting of two runs of nine attached to the two middle stringers, plus an adhoc clip at one location betweeen the stringers, rather than the 50 +/- stated); add notation on Poster Panel Side View as to location of any panel clip run other than the two shown. 5. Delete the reference to "actual size" on the panel clip detail (such size is not accurate for reproductions at anything other than 100%). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/11/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/11/2011 | SUE REEVES | REJECT SHELF | Completed |