The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10BU00194
Parcel: 12418276B

Review Status: Completed

Review Details: BILLBOARD-BLDG

Permit Number - T10BU00194
Review Name: BILLBOARD-BLDG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/24/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Billboard Modification Site Plan

1. Indicate that Sheet 2 is not part of the submittal; alternatively, add
"Sheet 2 of 2" on the Authorized Repair plan sheet.

Authorized Repair Plan (Drawing No.45-2071)

1. Amend note on plan that reads "No parts or components are to be removed,
installed, replaced and reinstalled" to read "No parts or components are to
be removed, installed, replaced or reinstalled" (i.e., change the "and" to
"or").
2. Add Note #11 from the Billboard Modification Site Plan to the face of the
repair plan: "There shall be no lighting installation, removal, relocation
or repair". [Note: separate lighting relocation permit has been issued
(T09EL02622); authorized repair under the permit applied for here
(T10BU000194) should be completed and final inspected prior to relocation of
light fixture from bottom to top]

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2010 SUE REEVES OUT TO CUSTOMER Completed
03/02/2010 SUE REEVES REJECT SHELF Completed