Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG
Permit Number - T10BU00194
Review Name: BILLBOARD-BLDG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/04/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/24/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Billboard Modification Site Plan 1. Indicate that Sheet 2 is not part of the submittal; alternatively, add "Sheet 2 of 2" on the Authorized Repair plan sheet. Authorized Repair Plan (Drawing No.45-2071) 1. Amend note on plan that reads "No parts or components are to be removed, installed, replaced and reinstalled" to read "No parts or components are to be removed, installed, replaced or reinstalled" (i.e., change the "and" to "or"). 2. Add Note #11 from the Billboard Modification Site Plan to the face of the repair plan: "There shall be no lighting installation, removal, relocation or repair". [Note: separate lighting relocation permit has been issued (T09EL02622); authorized repair under the permit applied for here (T10BU000194) should be completed and final inspected prior to relocation of light fixture from bottom to top] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/02/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
03/02/2010 | SUE REEVES | REJECT SHELF | Completed |