Permit Number: T10BU00149
Parcel: 132190060

Address:
2015 E BENSON HY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10BU00149
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair resubmittal for COT ID# 7 at
2015 East Benson Highway (T10BU00149). Please note that it is of particular
importance to inspect the existing dimensions of the torsion bar end plates
prior to removal to confirm the 1/2" thickness shown on the plan. There are
a few other such measurements as noted on the revised plan.in response to
Comment #8.

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. The face height dimension of 12'0" in the Frame Detail, now clarified to
include the trim as per Comment #5 on the original submittal, is not
consistent with the finished dimensions of the trim pieces described in the
Scope of Work (12'3", the standard dimension). The Frame Detail dimension
needs to conform. [Note: the BRC would not object to any mechanism that
would expedite permit issuance, but would still correct the dimension for
the record].

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2011 DELMA ROBEY OUT TO CUSTOMER Completed