Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T10BU00147
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/09/2011 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments on the authorized repair resubmittal for COT ID# 371 at 4006 East Speedway Boulevard (T10BU00147). Sheet 1 of 2 1. Conform Note #8 to amended Bullet #9 in the Scope of Work on Sheet 2. Sheet 2 of 2 1. The resubmittal needs to be under a registered engineer's stamp (as per Exhibit 12, Sec. 1(b)(4) of the Stipulation). 2. Add a date key for the revisions. 3. The resubmittal is not fully responsive to Comment #3 on the original submittal. Full dimensions need to be provided for the panel clip detail, not just the outer dimensions. 4. The resubmittal is not responsive to Comment #4 on the original submittal. More clearly specify the number of panel clips (the existing installation is 19 or so per face, consisting of two runs of nine attached to the two middle stringers, plus an very limited number of adhoc clips at locations between the stringers, rather than the 50 +/- stated); add notation on Poster Panel Side View as to location of any panel clip run other than the two shown. 5. Delete the reference to "actual size" on the panel clip detail (such size is not accurate for reproductions at anything other than 100%). |