Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10BU00147
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG

Permit Number - T10BU00147
Review Name: BILLBOARD-BLDG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/25/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Billboard Modification Site Plan

1. Indicate that Sheet 2 is not part of the submittal; alternatively, add
"Sheet 2 of 2" on the Authorized Repair plan sheet.
2. Billboard Note #2: change the street number from "4022" to "4006; the
correct street number as per Exhibit 1 of the settlement agreement (and the
original permit) is 4006.
3. Billboard #12: add specific reference to the scope of work in Billboard
Note #7.

Authorized Repair Plan (Drawing No.45-2068)

1. Amend note on plan that reads "No parts or components are to be removed,
installed, replaced and reinstalled" to read "No parts or components are to
be removed, installed, replaced or reinstalled" (i.e., change the "and" to
"or").
2. Title Block: change the street number from "4022" to "4006; the correct
street number as per Exhibit 1 of the settlement agreement (and the original
permit) is 4006.
3. Plan View: provide separate detail indicating material and dimensions of
panel section clip.
4. Stringer/Face Mounting; Poster Panel Side View: provide the total number
of existing panel clips to be removed and reinstalled per face and indicate
which stringers the clips are fastened to.
5. Scope of Work (Bullet 9): delete and insert in its place: "Existing light
fixtures are to remain on the site with no other fixtures (new or used) to
be installed".
6. Provide description of existing light fixtures and lamps to be removed
and reinstalled, including lamp type and catalog number, number of lamps,
and existing lamp lumen and ballast ratings.
7. Provide detail for existing and replacement clamps and fasteners that
attach the light fixture support arms to the billboard structure.
8. Identify the point of disconnect between the light fixture assembly to be
removed and reinstalled and the riser conduit.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/12/2011 SUE REEVES REJECT SHELF Completed