Permit Number: T09SA00220
Parcel: 130140260

Address:
4050 E 22ND ST

Review Status: Completed

Review Details: LUCAPPS - OVERLAY ZONE REV

Permit Number - T09SA00220
Review Name: LUCAPPS - OVERLAY ZONE REV
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2009 MATT FLICK ENGINEERING REVIEW Approved PDSD Engineering has no objection or adverse comment to approval of the ERR and WASH Overlay application. Furthermore, this Division does not believe forwarding of the application to SAC is necessary due to the documented lack of PRA within the development area.
08/14/2009 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond Subject to site plan and Special exception approval.
08/17/2009 DAVID RIVERA ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: David Rivera
Principal Planner

PROJECT: T09SA00220
Goodwill - Randolph Plaza
Special Overlay Application (WASH review)

TRANSMITTAL DATE: July 31, 2009

DUE DATE: August 26, 2009

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Zoning has reviewed the overlay application for the Goodwill development at the Randolph Plaza but cannot approve the plans at this time. Please address the following items and resubmit for review.

2. Zoning acknowledges that a Special Exception application was being processed and is close to final approval. As of this review date the Special exception had not been finaled and it is not clear what if any conditions of approval may have been attached to the approval. Until the final approval has been completed and copies of the conditions are provided and a site or development plan approval is completed the special application for the WASH review cannot be approved.

3. It is clear that no additional encroachment will occur therefore zoning does not have any comments related to the WASH application but does have comments related to the location of the wall and how it may affect the parking and / or PAALS in the area.

a. The masonry wall is to be constructed in front of the existing chain link fence which appears to place the existing parking spaces closer into the required PAAL if not into it. The vehicular use area on the plan submitted for the WASH review has not been dimensioned. Dimension the PAALs, parking spaces and wheel stop locations. Revise this plan to match the proposed site plan that is to be submitted for site review or the site plan / WASH plan can be inclusive. Dimension the parking lot areas along the west and south sides of the Goodwill Store.

b. Parking spaces adjacent to the buildings, walls, or property lines must be provided with wheel stops which must be placed 2.5 feet from the front of the parking spaces.

c. The proposed location of the trash enclosure and loading zones are being relocated and do not appear to be located in a location that provides sufficient access to / or maneuverability into either. Demonstrate that the dumpster will be accessible without driving over the loading zone. Demonstrate maneuverability into and out of the dumpster location using standard Radii of fifty foot outside and 35 inside radius. Contact Andy Vera with Environmental Services for more info and possible changes to access or Radii, 791-3175.

d. Demonstrate maneuverability in and out of the loading zone utilizing the same standards used for a refuse truck. See engineering comments for more info. (The loading zone must be accessible without crossing over parking spaces even when the spaces are not being used). A redesign of the locations for the loading zone and possibly the dumpster enclosure may be necessary to ensure compliance.

4. Clarify whether the existing chain link fence is to remain or will it be removed once the masonry wall is constructed.

5. Additional comments may be forthcoming based on changes to the plan and conditions of the approval of the Special Exception.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

C:\planning\cdrc\overlay\T09SA00220.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised plan and additional requested documents.
08/17/2009 PATRICIA GEHLEN ZONING-DECISION LETTER WRITE DECISION LETTER Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 17, 2009

Cindy Hogan
CDG Architects
2102 North Country Club Road #9
Tucson, Arizona 85716

Subject: T09SA00220 ERZ Overlay Zone for 4082 East 22nd Street

Dear George:

Your submittal of July 29, 2009 for the above project has been reviewed by the Community Design Review Committee and CONDITIONALLY APPROVED. The conditions of approval are as follows: 1) closure of the public comment period and 2) approval by the DSD Director.



PRIOR TO SITE PLAN APPROVAL, THE OVERLAY CASE NUMBER MUST BE LISTED ON ALL SHEET OF THE SITE, LANDSCAPE AND NPPO PLANS IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. IN ADDITION, A NOTE MUST BE ADDED TO THE SITE PLAN THAT LISTS THE CASE NUMBER, TYPE OF OVERLAY, DATE OF APPROVAL AND CONDITIONS IMPOSED, IF ANY.







Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Y. Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/


Via fax: 798-3341