Plan Number: T09PI00012
Parcel: Unknown

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T09PI00012
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2009 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Completed
04/08/2009 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Passed
04/16/2009 GARY WITTWER DOT LANDSCAPE REVIEW Approved
05/06/2009 Blanca Espino DOT ENGINEERING REVIEW Denied PIA Plan
1. Please include a detail letter of explanation with the next submittal indicating where and how revisions were made. Single word responses are unacceptable. Include plans/redlines from previous plan submittal.

2. In title block, remove the text Transportation Planning & Landscape Architect.

3. In title block, add assigned I-Plan Number, I-2009-016 to all sheets.

4. Indicate assigned DSD activity number T09PI000012 above title block. See redlines.

5. Indicate the Administrative address. The physical site's address.

6. Indicate the correct address of the owner. 201 N. Stone Ave. is known as the Public Works Building.

7. Add note to the Paving Notes:
Floodplain Use Permit No._______, has been issued for work impacting City Floodplains.

8. A City Floodplain Use Permit will be required for road construction from COT - DSD Engineering.

9. The project may negatively impact abutting property owners. Per the approved Grading Plan, Sheet 2A of 18, existing sheet flow impacting the proposed development and flowing across the proposed development, will now be channelized along the east edge of the development south, then turned west, directing the concentrated flow onto private property. COT records show this flow is a COT Administrative Floodplain. South Naco Vista is a COT Flood Hazard area, at a corresponding Q-100 of 130-cfs.

10. The proposed road design shows that the drainage has been altered. Demonstrate on how the off-site discharge will not impact adjacent properties.

11. The proposed road design shows a crown street design. Demonstrate how the 10-year runoff is to be contained within the curbs of the street.

12. A proposed speed table is to replace the existing one. Demonstrate how the speed table and curbing will contain the flow within the roadway without creating flooding upstream and or to adjacent properties. Justify speed table replacement within a crown street design.

13. Sheet 2, Indicate the street names and stationings at the Naco Vista and Hidalgo Vista. See redlines.

14. Sheet 2, Sta. 10+24.13; "New sidewalk to abut to existing sidewalk/bus shelter pad." Demonstrate that an unobstructed 5-foot wide pedestrian pathway will be provided where the new sidewalk meets the bus pad and structure.

15. Sheet 2, Sta. 10+20.20; Connect 6" reveal curb to existing. Indicate existing terminal section is to be removed. See redlines.

16. Sheet 2, Indicate the proposed curb radius. See redlines.

17. Sheet 2, Provide a survey monument at the intersection of Hancock Vista & Naco Vista. See redlines.

18. Sheet 2, Indicate the Beginning and Ending points for the Saw-Cut, Trim, Tack and Join to match existing pavement. Also indicate Stationing, Offset and Elevations. See redlines.

19. Sheet 2, Concrete header is to be 24LF. Correct. See redlines.

20. Sheet 2, Profile view; Show the speed table location. See redlines.

21. Sheet 3, Detail 2; Indicate the recommended pavement structural design per the Geotechnical Report. Indicate % amount for compacted subgrade. Correct date for Geotechnical Report.

22. Sheet 3, Detail 4; Indicate if the proposed handicap ramp is Typical, Limited Right-of-Way or Modified in the Pima County/City of Tucson Standard Details for Public Improvements, 2003 Edition. Correct detail.

23. Sheet 3, Detail 4; The handicap ramp is to have a minimum 5' x 5' landing. Dimension and label landing area.

24. Sheet 3; Detail 3; General Note #12 shall read, Contractor responsible to stripe speed humps and speed table with 12" wide white thermoplastic paint or reflectorized tape.

25. Sheet 3, Detail 3; See attached details to be added per Zelin Canchola.

26. Submit plans to COT/DSD-Engineering for Plan/Floodplain review.

27. See redlines for additional corrections.

Drainage Report
28. The project may negatively impact abutting property owners. Per the approved Grading Plan, Sheet 2A of 18, existing sheet flow impacting the proposed development and flowing across the proposed development, will now be channelized along the east edge of the development south, then turned west, directing the concentrated flow onto private property. COT records show this flow is a COT Administrative Floodplain. South Naco Vista is a COT Flood Hazard area, at a corresponding Q-100 of 130-cfs.

29. The proposed road design shows that the drainage has been altered. Demonstrate on how the off-site discharge will not impact adjacent properties.

30. The proposed road design shows a crown street design. Demonstrate how the 10-year runoff is to be contained within the curbs of the street.

31. A proposed speed table is to replace the existing one. Demonstrate how the speed table and curbing will contain the flow within the roadway without creating flooding upstream and or to adjacent properties. Justify speed table replacement within a crown street design.


Once changes, modifications, and or corrections are made to the PIA plan resubmitted and reviewed, further comment may result. If you have any questions, I can be reached at 837-6634 or Blanca.Espino@tucsonaz.gov
05/08/2009 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond We have reviewed this plan and have the following comment:

1. The pavement section calls for 2" of AC over 4" of ABC. Please verify that this is adequate.

HP & PR
05/12/2009 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED Completed
05/12/2009 JOSE ORTIZ DOT TRAFFIC REVIEW Approv-Cond Along Naco Vista ensure that all existing signs that are effected by the off-site improvements and are applicable to the roadway remain in place or relocated to an appropriate location. If damaged or unsuitable for reuse then replace with new sign and/or post.
05/12/2009 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed