Plan Number: T09PI00003
Parcel: Unknown

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T09PI00003
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2009 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/02/2009 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS
02/25/2009 RICHARD LEIGH DOT ENGINEERING REVIEW Denied February 24, 2009

SUBJECT: Valencia Road and Nogales Highway Offsite Improvements for Circle K, PIA T09PI0003

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Include the plan number "I-2009-006" in title block of each sheet.

2. Include Development Services Department PIA activity number "T09PI0003"on cover sheet.

3. Place title of plan in each title block of the plan set. Title blocks should be identical except for sheet number. Extraneous labeling such as sheet details or street names should be labeled above title block.

4. Verify that all line work used is included in legend.

5. Provide a cross section for Valencia Road and Nogales Highway. Indicate existing and proposed roadway cross slopes.

6. Provide a structural pavement section for proposed pavement widening.

7. A concrete bus bay per ADOT Standard Detail C-05.50 will have to be provided. Provide complete details of bus bay.

8. Provide a dimensioned detail of each type of curb access ramp proposed and indicate the use of truncated domes as the tactile warning device.

9. Have the flows in the proposed channel, on the southwest corner of Valencia Rd and Nogales Highway, originally been discharged on Valecia Road? According to the existing topography, it appears that these flows originally entered the project site at a low point at approximately Sta. 3185+61, LT. (Nogales Highway). Has accepting the majority of flows at the existing low point and conveying the remaining flows along the gutter to Valencia Road been explored? What are the magnitudes of these flows? Submit supporting hydrologic data with next submittal.

10. Provide additional details for the required bus shelter on Nogales Highway. Has COT Transit Services been consulted for the construction for the proposed bus shelter?

11. Provide a Curb terminal section per PC/COT Std. Dtl. 210 at station 3184+53.33, 36.64', LT (Nogales Highway).

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
03/04/2009 GARY WITTWER DOT LANDSCAPE REVIEW Approved
03/05/2009 JOSE ORTIZ DOT TRAFFIC REVIEW Denied March 5, 2009
ACTIVITY NUMBER: T09PI00003
PROJECT NAME: Circle K
PROJECT ADDRESS: 530 E Valencia Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

3. Along Valencia and Nogales HWY ensure that all existing signs that are effected by the off-site improvements and are applicable to the roadway remain in place or relocated to an appropriate location. If damaged or unsuitable for reuse, then replace with new sign and/or post (i.e. the speed limit sign on Nogales HWY).

4. Provide a drawing to address the relocation of lighting along Valencia Road.

5. Provide a drawing to address the relocation/modification of the traffic signal.



If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
03/05/2009 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
03/13/2009 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED Completed
03/13/2009 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed