Permit Review Detail
Review Status: Completed
Review Details: C OF O
Permit Number - T09OT02740
Review Name: C OF O
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Parking and landscaping must be brought up to the standard provided on the last approved site plan (per C. Gross). |
| 12/16/2009 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | THIS IS A CHANGE OF USE FROM B TO A-3 OCCUPANT LOAD GOES UP TO 146 EACH LARGE ROOM USED FOR ASSEMBLY WILL REQUIRE 2 EXITS SPACED APART A MINIMUM OF 1/2 THE TRAVEL DISTANCE. EGRESS DOORS MUST SWING IN THE DIRECTION OF TRAVEL. 2 ACCESSIBLE RESTROOMS ARE REQUIRED. INTERNALLY ILLUMINATED EXIT SIGNS AND EMERGENCY EGRESS LIGHTING WILL BE REQUIRED. |