Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T09OT02340
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/24/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | November 24, 2009 FLOODPLAIN USE PERMIT NO.: T09OT02340 ADDRESS: 4060 E River Road, Tucson Arizona 85718 PROPERTY OWNER: Pima County 201 N Stone Ave, Tucson Arizona 85701 The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone A per the Flood Insurance Rate Maps 04019C1644K, specifically described as: A portion of Parcel 110-02-015E, IRR PCL IN E2 E2 W2 NW4 LYG S OF RIVER RD 2.85 AC SEC 27-13-14 For the purpose installing and operating antennas and associated equipment cabinets for NEXTG. In reviewing this Floodplain Use Permit application it has been concluded that the improvements fall under Chapter 26 Section 26-4.8. Statutory Exemptions for the construction and erection of poles, towers, foundations, guy wires and other facilities related to power transmission. The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard Area Regulations. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require application for review and approval of an additional Floodplain Use Permit. 1) Due to the location of the FEMA unnumbered A Zone (undetermined flood height) it is recommended that the Equipment Cabinet be elevated 1 foot above the calculated water surface elevation (or minimum 2-feet above highest adjacent grade). Or that the cabinet used be rated so that is can be submerged in flood waters for 1 hour duration during a 1% chance flood event. APPLICANT NAME: David Kirdell ADDRESS: 3818 N Highway Drive, Tucson Arizona 85705 PHONE: 520-334-9056 CONTRACTOR: HP Communication Inc. ADDRESS: 3818 N Highway Drive, Tucson Arizona 85705 PHONE: 520-334-9056 SIGNATURE OF APPLICANT DATE The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions. |